Parameters
List of parameters
1-258
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays control word 1 of the infeed.
Note: OC: Operating condition
Description: Displays the control word of the sequence control.
Note: OC: Operating condition
Description: Displays the control word of the sequence control.
r0898.0...10 CO/BO: Control word sequence control infeed / STW seq_ctrl INF
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 8720
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
10 Master ctrl by PLC Yes No -
r0898.0...14 CO/BO: Control word sequence control / STW seq_ctrl
SERVO, VECTOR Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2501
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Enable operation Yes No -
04 Enables the ramp-function generator Yes No -
05 Freeze ramp-function generator No Yes -
06 Enable speed setpoint Yes No -
07 Command open brake Yes No -
08 Jog 1 Yes No -
09 Jog 2 Yes No -
10 Master ctrl by PLC Yes No -
12 Speed controller enable Yes No -
14 Command close brake Yes No -
r0898.0...14 CO/BO: Control word sequence control / STW seq_ctrl
SERVO (Lin) Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2501
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Enable operation Yes No -
04 Enables the ramp-function generator Yes No -
05 Freeze ramp-function generator No Yes -
06 Enable velocity setpoint Yes No -