Siemens SINAMICS S Series - p2238[0...n] Technology controller motorized potentiometer minimum value; Tec_ctrl mop min; p2240[0...n] Technology controller motorized potentiometer starting value; Tec_ctrl mop start; r2245 CO: Technology controller mot. potentiometer setpoint before RFG; Tec_ctr mop befRFG; p2247[0...n] Technology controller motorized potentiometer ramp-up time; Tec_ctr mop t_r�up

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-612
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the minimum value for the motorized potentiometer of the technology controller.
Dependency: Refer to: p2237
Description: Sets the starting value for the motorized potentiometer of the technology controller.
For p2230.0 = 0, this setpoint is entered after ON.
Dependency: Refer to: p2230
Description: Sets the effective setpoint in front of the internal motorized potentiometer ramp-function generator of the technology
controller.
Dependency: Refer to: r2250
Description: Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency: Refer to: p2248
Note: The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
p2238[0...n] Technology controller motorized potentiometer minimum value / Tec_ctrl mop min
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] -100.00 [%]
p2240[0...n] Technology controller motorized potentiometer starting value / Tec_ctrl mop start
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 0.00 [%]
r2245 CO: Technology controller mot. potentiometer setpoint before RFG /
Tec_ctr mop befRFG
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 7954
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p2247[0...n] Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [s] 1000.0 [s] 10.0 [s]