Function Diagrams
Safety Integrated
2-1218
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-106 2848 – Extended functions, TM54F configuration, F-DI/F-DO test
- 2848 -
Function diagram
87654321
fp_2848_51_eng.vsd
DO: TM54F_MA, TM54F_SL
SINAMICS
19.06.07 V02.05.01
Safety Integrated - Extended Functions, TM54F Configuration, F-DI/F-DO Test
p10000 (12.00 ms)
Drive 1
p10011[0] (1)
Drive 2
p10011[1] (1)
Drive 3
p10011[2] (1)
Drive 4
p10011[3] (1)
Drive 5
p10011[4] (1)
Drive group assignment
SI FrcdCkProcTimer
0.00...8760.00 [h]
p10003 (8.00)
(0)
SI DI fcp F-DO
p10007
T0
Drive group 1
Drive group 2
Drive group 3
Drive group 4
Drive 6
p10011[5] (1)
A35012
“Test stop activ“
F35013
“Test stop error“
A35014
“Test stop required“
Test F-DI
Test F-DO
SI F-DI enab test
p10041
SI test sens FS
p10046
Test stop
Restart timer (on successful test stop)
r10053.3 DI 23
r10053.0 DI 20
r10053.1 DI 21
r10053.2 DI 22
p10010[0]
Drive 1
p10010[1]
Drive 2
p10010[2]
Drive 3
p10010[3]
Drive 4
p10010[4]
Drive 5
p10010[5]
Drive 6
[2853.8]
[2853.8]
[2853.8]
[2853.8]