List of parameters
Parameters
1-283
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
r0975[6] = 9 --> PROFIdrive drive object sub-type class 1
r0975[7] = 2 --> drive object number = 2
r0975[8] = 0 (reserved)
r0975[9] = 0 (reserved)
r0975[10] = 600 --> second part, firmware version (complete version: V01.02.06.00)
Description: Resets or downloads all parameters of the drive system.
Values: 0: Inactive
1: Starts to reset all parameters to factory setting
2: Starts to download param. saved in non-volatile way w/ p0977 = 1
3: Start to download the volatile parameters from RAM
10: Starts to download param. saved in non-volatile way w/ p0977=10
11: Starts to download param. saved in non-volatile way w/ p0977=11
12: Starts to download param. saved in non-volatile way w/ p0977=12
20: Starts to download Siemens internal setting 20
21: Starts to download Siemens internal setting 21
22: Starts to download Siemens internal setting 22
23: Starts to download Siemens internal setting 23
24: Starts to download Siemens internal setting 24
25: Starts to download Siemens internal setting 25
26: Starts to download Siemens internal setting 26
100: Starts to reset all BICO interconnections
1011: Starts to download param. saved in volatile way w/ p0977 = 1011
1012: Starts to download param. saved in volatile way w/ p0977 = 1012
1013: Starts to download param. saved in volatile way w/ p0977 = 1013
Note: After all of the parameters have been reset to their factory setting, the system must commissioned for the first time
again.
Resetting or loading is realized in the non-volatile memory.
Procedure:
1. Set p0009 = 30 (parameter reset).
2. Set p0976 to "required value". The system is rebooted.
p0976 is automatically set to 0 and p0009 is automatically set to 1 after this has been carried out.
Description: Saves all parameters of the drive system to the non-volatile memory (CompactFlash card).
Values: 0: Inactive
1: Save in non-volatile fashion - downloaded at POWER ON
10: Save as opt. in non-vol. fashion - downloaded w/ p0976=10
11: Save as opt. in non-vol. fashion - downloaded w/ p0976=11
12: Save as opt. in non-vol. fashion - downloaded w/ p0976=12
20: Save in a non-volatile fashion as setting 20 (reserved)
21: Save in a non-volatile fashion as setting 21 (reserved)
22: Save in a non-volatile fashion as setting 22 (reserved)
p0976 Reset and load all parameters / Reset load all par
CU_CX32, CU_S Can be changed: C1(30) Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Factory settings Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1013 0
p0977 Save all parameters / Save all par
CU_CX32, CU_S Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Factory settings Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1013 0