EasyManua.ls Logo

Siemens SINAMICS S Series - Figure 2-227 8820 - Control word sequence control infeed

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function Diagrams
Smart Infeed
2-1354
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-227 8820 – Control word sequence control infeed
- 8820 -
Function diagram
87654321
fp_8820_01_eng.vsd
DO: S_INF
SINAMICS S
07.07.06 V02.05.00
Smart Infeed - Control word, sequence control infeed
p0844[C] (1)
1 OFF2 (electrical)
p0845[C] (1)
2 OFF2 (electrical)
11
12
13
14
15
p0840[C] (0)
p0852[C] (1)
9
10
8
7
6
5
4
3
2
1
0
Bit No.
<2>
<2> PROFIdrive interconnection: For the manufacturer-specific
PROFIdrive telegram, the upper input is connected to
PROFIdrive signal A_STW1 [2447]. This only involves CDS0.
p0115[3] (2000.00 µs)
To the control unit [8832]
r0898.0
To the control unit [8832]r0898.1
To the control unit [8832]r0898.3
r0898.10
r0898.6
p0854[C] (0)
p3533[C] (0)
r0898
STW seq_ctrl INF
= ON (close pre-charging/line contactor, pulses can be enabled)
0 = OFF1 (pulse cancellation and open pre-charging/line contactor)
Control word sequence control infeed
1 = Operating condition no OFF2 (enable is possible)
0 = OFF2 (immediate pulse cancellation, open pre-charging/line contactor and power-on inhibit)
Reserved
1 = Enable operation (pulses can be enabled)
0 = Inhibit operation (cancel pulses)
Reserved
Reserved
Reserved
Reserved
Reserved
1 = Control via PLC
1 = Inhibit regenerative operation
Reserved
Reserved
Reserved
Reserved
<1>
Reserved
<3> Is pre-defined via the PC if the master control is retrieved.
<3>
<3>
<3>
<3>
<1> To ensure that the drive objects accepts the process data
(PZD), bit 10 must be set in the first PZD word.

Table of Contents

Related product manuals