Siemens SINAMICS S Series - p1523[0...n] CI: Torque limit lower; M_max lower; p1524[0...n] CO: Torque limit upper;motoring scaling; M_max up;mot scal; p1524[0...n] CO: Force limit upper;motoring scaling; F_max up;mot scal

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-430
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the signal source for the lower torque limit.
Dependency: Refer to: p1520, p1521, p1522
Danger: Positive values. that are obtained as a result of the signal source and the scaling can cause the motor to accelerate
in an uncontrollable fashion.
Description: Sets the scaling for the upper torque limit or the torque limit when motoring.
Dependency: p1400 bit 4 = 0: Upper / lower
p1400 bit 4 = 1: Motoring / generating
Notice: A BICO interconnection to a parameter that belongs to a drive objects always acts on the effective data set.
Note: This parameter can be freely interconnected.
The value has the above significance if it is interconnected from connector input p1528.
Description: Sets the scaling for the upper force limit or the force limit when motoring.
Dependency: p1400 bit 4 = 0: Upper / lower
p1400 bit 4 = 1: Motoring / generating
Notice: A BICO interconnection to a parameter that belongs to a drive objects always acts on the effective data set.
Note: This parameter can be freely interconnected.
The value has the above significance if it is interconnected from connector input p1528.
p1523[0...n] CI: Torque limit lower / M_max lower
VECTOR (n/M) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 6630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 1521[0]
p1524[0...n] CO: Torque limit upper/motoring scaling / M_max up/mot scal
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5620, 5630,
6630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
-2000.0 [%] 2000.0 [%] 100.0 [%]
p1524[0...n] CO: Force limit upper/motoring scaling / F_max up/mot scal
SERVO (Lin) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5620, 5630,
6630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
-2000.0 [%] 2000.0 [%] 100.0 [%]