Description: Sets the fault response for the selected fault.
Values: 0: NONE
1: OFF1
2: OFF2
3: OFF3
4: STOP1 (being developed)
5: STOP2
6: IASC / DC BRAKE
7: ENCODER (p0491)
Dependency: The fault is selected and the required response is set under the same index.
Refer to: p2100
Notice: It is not possible to re-parameterize the response to a specific fault for faults that are already present (queued).
Note: OFF1:
Braking along the ramp-function generator down ramp followed by a pulse inhibit.
OFF2:
Internal/external pulse inhibit.
OFF3:
Braking along the OFF3 down ramp followed by a pulse inhibit.
STOP2:
n_set = 0
The fault response can only be changed for faults with the appropriate identification.
IASC / DC BRAKE:
a) For synchronous motors (p0300 = 2xx, 4xx), an internal armature short-circuit is executed.
b) For induction motors (p0300 = 1xx)
Example:
F12345 and fault response = NONE (OFF1, OFF2) --> The NONE fault response can be changed to either OFF1 or
OFF2.
p2101[0...19] Setting the fault response / Fault response