List of parameters
Parameters
1-387
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: The velocity setpoint filter is parameterized using p1415 ... p1420 and p1421 ... p1426.
Description: Activates speed setpoint filter 1 for the incremental encoder emulation.
Dependency: The speed setpoint filter can be parameterized using p1417 and p1418.
Refer to: p1417, p1418
Description: Sets the type for speed setpoint filter 1.
Values: 0: Low pass: PT1
1: Low pass: PT2
2: General 2nd-order filter
Dependency: PT1 low pass: p1416
PT2 low pass: p1417, p1418
General filter: p1417 - p1420
Description: Sets the type for speed setpoint filter 1.
Values: 0: Low pass: PT1
1: Low pass: PT2
2: General 2nd-order filter
Dependency: PT1 low pass: p1416
PT2 low pass: p1417, p1418
General filter: p1417 - p1420
Bit field: Bit Signal name 1 signal 0 signal FP
00 Activate filter 1 Yes No -
01 Activate filter 2 Yes No -
p1414[0...n] Speed setpoint filter activation / n_set_filt active
TM41 Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: DDS, p0180 Func. diagram: 9674
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Activate filter 1 Yes No 9674
p1415[0...n] Speed setpoint filter 1 type / n_set_filt 1 typ
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: 5020
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0 2 0
p1415[0...n] Velocity setpoint filter 1 type / n_set_filt 1 typ
SERVO (Lin) Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: 5020
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0 2 0