Siemens SINAMICS S Series - r1344 I_max controller voltage output; I_max_ctrl V_outp; p1345[0...n] I_max voltage controller proportional gain; I_max_V_ctrl Kp; p1346[0...n] I_max voltage controller integral time; I_max_V_ctrl Tn; p1349[0...n] V;f mode resonance damping maximum frequency; Uf res_damp F_max

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-377
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the amount by which the converter output voltage is reduced.
Dependency: Refer to: p1340
Description: Sets the proportional gain for the I_max voltage controller.
Dependency: Refer to: p1340
Note: The controller settings are also used in the current controller of the DC brake (refer to p1232).
Description: Sets the integral time for the I_max voltage controller.
Dependency: Refer to: p1340
Note: p1346 = 0: Integral time of the I_max voltage controller de-activated.
The controller settings are also used in the current controller of the DC brake (refer to p1232).
Description: Sets the maximum output frequency above which the resonance damping for V/f control is de-activated.
Dependency: Refer to: p1338, p1339
Note: For p1349 = 0, the changeover limit is automatically set to 95 % of the rated motor frequency - however, to a max.
of 45 Hz.
r1344 I_max controller voltage output / I_max_ctrl V_outp
VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 1690
P-Group: V/f open-loop control Units group: 5_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
p1345[0...n] I_max voltage controller proportional gain / I_max_V_ctrl Kp
VECTOR Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 1690
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 100000.000 0.000
p1346[0...n] I_max voltage controller integral time / I_max_V_ctrl Tn
VECTOR Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 1690
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 50.000 [s] 0.030 [s]
p1349[0...n] V/f mode resonance damping maximum frequency / Uf res_damp F_max
VECTOR Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6310
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]