List of parameters
Parameters
1-937
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the drive object selection (index 0), the sub-index area (index 1) and the parameter area (index 2) when using
virtual objects.
This means that it is possible to access all SINAMICS parameters via CAN.
Index 0 (drive object selection):
0: Not possible to access virtual CANopen objects
1: Device
2 ... 65535: Drive 1 ... 8
Index 1 (sub-index area):
0: 0 ... 255
1: 256 ... 511
2: 512 ... 767
3: 768 ... 1023
Index 2 (parameter area):
0: 1 ... 9999
1: 10000 ... 19999
2: 20000 ... 29999
3: 30000 ... 39999
Index: [0] = Drive object selection
[1] = Sub-index range
[2] = Parameter range
Description: Sets the drive behavior if a CAN communication error occurs.
Values: 0: No response
1: OFF1
2: OFF2
3: OFF3
Dependency: Refer to: F08700
Description: Displays the register of the CAN controller C_CAN:
Register, Message Interface Register and Message Handler Register - referred to the CAN protocol.
p8630[0...2] CBC virtual objects / Virtual objects
CU_S (CAN) Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 65535 0
p8641 CBC abort connection option code / Abort con opt code
SERVO (CAN), VEC-
TOR (CAN)
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 3 3
r8680[0...36] CBC diagnostics hardware / Diagnostics HW
CU_S (CAN) Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -