Siemens SINAMICS S Series - p1756 Motor model changeover speed hysteresis sensorless operation; MotMod n_chgov hys; p1757[0...n] Motor model w;o enc. op.;cl.-loop controlled stab. controller Kp; MotMod w;o enc Kp; p1758[0...n] Motor model changeover delay time closed;open-loop control; MotMod t cl_op; p1759[0...n] Motor model changeover delay time open;closed loop control; MotMod t op_cl

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-476
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the hysteresis for the changeover speed of the motor model for sensorless operation.
Dependency: Refer to: p1755
Note: The parameter value refers to p1755.
Description: Sets the gain of the transient response controller when the motor model changes over from open-loop controlled
operation to closed-loop controlled operation.
Note: Only for ASM and PSM in sensorless operation:
The settling range starts at 0.5 * p1755 * p1756.
For ASM it ends at p1755 * p1756 or at p1755, if p1759 is at the maximum value.
For PSM it always ends at p1755 * p1756.
Description: Sets the minimum time for falling below the changeover speed when changing from closed-loop controlled opera-
tion to open-loop controlled operation.
Dependency: Refer to: p1755, p1756
Description: Sets the minimum time for exceeding the changeover speed when changing from open-loop controlled operation to
closed-loop controlled operation.
Dependency: Refer to: p1755, p1756
p1756 Motor model changeover speed hysteresis sensorless operation /
MotMod n_chgov hys
VECTOR Can be changed: U, T Calculated: CALC_MOD_REG Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.0 [%] 95.0 [%] 50.0 [%]
p1757[0...n] Motor model w/o enc. op./cl.-loop controlled stab. controller Kp / MotMod w/o enc Kp
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL, FEM Expert list: 1
Min Max Factory setting
0.01 10.00 0.70
p1758[0...n] Motor model changeover delay time closed/open-loop control / MotMod t cl_op
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
100 [ms] 10000 [ms] 1000 [ms]
p1759[0...n] Motor model changeover delay time open/closed loop control / MotMod t op_cl
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
0 [ms] 2000 [ms] 0 [ms]