Siemens SINAMICS S Series - r7224[0...n] CO: Par_circuit phase current actual value phase V; I_phase V act val; r7225[0...n] CO: Par_circuit phase current actual value phase W; I_phase W act val; r7226[0...n] CO: Par_circuit phase current actual value phase U offset; I_phase U offset; r7227[0...n] CO: Par_circuit phase current actual value phase V offset; I_phase V offset

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-900
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the measured actual value of phase V as peak value.
The summed value of all power units is displayed in r0069[1].
Description: Displays the measured actual value of phase W as peak value.
The summed value of all power units is displayed in r0069[2].
Description: Displays the measured offset of phase U as peak value.
The summed value of all power units is displayed in r0069[3].
Description: Displays the measured offset of phase V as peak value.
The summed value of all power units is displayed in r0069[4].
Description: Displays the measured offset of phase W as peak value.
The summed value of all power units is displayed in r0069[5].
r7224[0...n] CO: Par_circuit phase current actual value phase V / I_phase V act val
A_INF (Parallel),
S_INF (Parallel),
VECTOR (Parallel)
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r7225[0...n] CO: Par_circuit phase current actual value phase W / I_phase W act val
A_INF (Parallel),
S_INF (Parallel),
VECTOR (Parallel)
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r7226[0...n] CO: Par_circuit phase current actual value phase U offset / I_phase U offset
A_INF (Parallel),
S_INF (Parallel),
VECTOR (Parallel)
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r7227[0...n] CO: Par_circuit phase current actual value phase V offset / I_phase V offset
A_INF (Parallel),
S_INF (Parallel),
VECTOR (Parallel)
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r7228[0...n] CO: Par_circuit phase current actual value phase W offset / I_phase W offset
A_INF (Parallel),
S_INF (Parallel),
VECTOR (Parallel)
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]