EasyManua.ls Logo

Siemens SINAMICS S Series - p0491 Motor encoder fault response ENCODER; Fault resp ENCODER; p0492 Square-wave encoder, maximum speed difference per sampling cycle; n_dif max;samp_cyc

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-197
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Caution: For p0491 = 1.4 the following must be carefully observed:
In spite of the motor encoder fault that has occurred, the motor is still operated.
Note: For a value 1, 2, 3, the following applies:
Encoderless operation must have been commissioned.
Refer to the status signal "sensorless operation due to a fault" (BO: r1407.13).
If, when setting r1407.13, a different drive data set is selected (e.g. interconnection from p0820), then the open-loop
or closed-loop control type p1300 of this data set must match the original data set (e.g. p1300 = 21). Sensorless
closed-loop controlled operation is kept when changing over.
For sensorless operation (p1404 = 0 or p1300 = 20), the following applies:
- The following condition must be fulfilled: p1800 >= n / (2 * p0115[0]), n = 1, 2, ...
- For motors with a small power rating (< 300 W) we recommend to set n >= 2.
Description: Sets the behavior for the ENCODER fault response (motor encoder).
This means, for example, if an encoder fault occurs, sensorless operation can be automatically selected with a
shutdown behavior that can be selected.
Values: 0: Encoder fault results in OFF2
1: Enc fault results in sensorless oper. and oper. continues
2: Encoder fault results in sensorless operation and OFF1
3: Encoder fault results in sensorless operation and OFF3
4: Encoder fault results in an int. armature short-cct. / DC brake
Dependency: The following parameters are relevant for sensorless operation.
Refer to: p0341, p0342, p1470, p1472, p1517, p1612, p1755
Refer to: F07575
Caution: For p0491 = 1.4 the following must be carefully observed:
In spite of the motor encoder fault that has occurred, the motor is still operated.
Note: For a value 1, 2, 3, the following applies:
Encoderless operation must have been commissioned.
Refer to the status signal "sensorless operation due to a fault" (BO: r1407.13).
Not possible for separately excited synchronous motors (p0300 = 5).
Description: Maximum permissible speed difference between two computation cycles when evaluating square-wave encoders.
When the value is exceeded, depending on p0491, either sensorless closed-loop speed/torque control is selected
or the drive is powered-down.
p0491 Motor encoder fault response ENCODER / Fault resp ENCODER
VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 4 0
p0492 Square-wave encoder, maximum speed difference per sampling cycle /
n_dif max/samp_cyc
SERVO, VECTOR Can be changed: U, T Calculated: CALC_MOD_REG Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [RPM] 210000.0 [RPM] 0.0 [RPM]

Table of Contents

Related product manuals