List of parameters
Parameters
1-823
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the sampling time for the inputs and outputs of terminal module 15 (TM15).
Dependency: The parameter can only be modified for p0009 = 3, 29.
Refer to: p0009, r0110, r0111
Note: - the modified sampling time is not effective until the drive unit is powered-up again.
- P4099(0) must never equal zero.
Description: Sets the temperature evaluation of terminal module 31 (TM31).
This means that the temperature sensor type is selected and the evaluation is switched-in.
Values: 0: Evaluation disabled
1: PTC thermistor
2: KTY84
Note: The temperature sensor is connected at terminals X522.7(+) and X522.8(-).
Description: Displays the actual resistance value of the temperature sensor connected at terminal module 31 (TM31).
Note: The temperature sensor is connected at terminals X522.7(+) and X522.8(-).
The maximum measurable resistance value is approx. 1700 Ohm.
Description: Sets the fault/alarm threshold for the temperature evaluation of terminal module 31 (TM31).
Temperature actual value > p4102[0] --> alarm A35211 is output.
Temperature actual value > p4102[1] --> fault F35207 is output.
p4099 TM15DI/DO inputs/outputs, sampling time / TM15D I/O t_sampl
TM15DI_DO Can be changed: C1(3) Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9400, 9401,
9402
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 5000.00 [µs] 4000.00 [µs]
p4100 TM31 temperature evaluation, sensor type / TM31 temp sens_typ
TM31 Can be changed: T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: 9576, 9577
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 2 0
r4101 TM31 temperature evaluation, sensor resistance / TM31 temp R_sensor
TM31 Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 9576, 9577
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Ohm] - [Ohm] - [Ohm]
p4102[0...1] TM31 temperature evaluation fault/alarm threshold / TM31 temp thresh
TM31 Can be changed: T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: 9576
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-48 [°C] 251 [°C] [0] 100 [°C]
[1] 120 [°C]