List of parameters
Parameters
1-883
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the scaling for the amplitude of the signal waveforms separately for each output channel.
The value cannot be changed while the function generator is running.
Index: [0] = First drive for connection
[1] = Second drive for connection
[2] = Third drive for connection
Description: Sets the scaling for the offset of the signal waveforms separately for each output channel.
The value cannot be changed while the function generator is running.
Index: [0] = First drive for connection
[1] = Second drive for connection
[2] = Third drive for connection
Description: Displays the status word of the sequence control from terminal module 41 (TM41).
p4832[0...2] Function generator amplitude scaling / FG amplitude scal
CU_CX32, CU_S Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-340.28235E36 [%] 340.28235E36 [%] 100.00000 [%]
p4833[0...2] Function generator offset scaling / FG offset scal
CU_CX32, CU_S Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-340.28235E36 [%] 340.28235E36 [%] 100.00000 [%]
r4899 Status word sequence control / ZSW seq_ctrl
TM41 Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Ready to power up Yes No -
01 Ready Yes No -
02 Operation enabled Yes No -
03 Fault present Yes No -
04 Coast down active No Yes -
05 Quick Stop active No Yes -
06 Power-on inhibit Yes No -
07 Alarm present Yes No -
09 Control requested Yes No -
14 Motor rotates forwards Yes No -