Parameters
List of parameters
1-312
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
For vector control (p1300 = 20 ... 23) the maximum speed is limited to 60.0 / (8.333 * p0115[0] * r0313). This can be
identified by a reduction in r1084. p1082 is not changed in this process due to the fact that the operating mode
p1300 can be changed over.
Description: Sets the maximum speed for the positive direction.
Notice: A BICO interconnection to a parameter that belongs to a drive objects always acts on the effective data set.
Description: Sets the maximum velocity for the positive direction.
Notice: A BICO interconnection to a parameter that belongs to a drive objects always acts on the effective data set.
Description: Displays the effective positive speed limit.
Dependency: Refer to: p1082, p1083, p1085
Description: Displays the effective positive velocity limit.
Dependency: Refer to: p1082, p1083, p1085
p1083[0...n] CO: Speed limit in positive direction of rotation / n_limit pos
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [RPM] 210000.000 [RPM] 210000.000 [RPM]
p1083[0...n] CO: Velocity limit positive direction / v_limit pos
SERVO (Lin) Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [m/min] 1000.000 [m/min] 1000.000 [m/min]
r1084 Speed limit positive effective / n_limit pos eff
SERVO, VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 3050, 5030,
5210, 6640, 7020, 8010
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [RPM] - [RPM] - [RPM]
r1084 Velocity limit positive effective / v_limit pos eff
SERVO (Lin) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 3050, 5030,
5210, 6640, 7020, 8010
P-Group: Setpoints Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [m/min] - [m/min] - [m/min]