List of parameters
Parameters
1-723
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the output voltages of the harmonics controller.
r3626[0]: RMS value of the 5th harmonic of the controller output voltage
r3626[1]: RMS value of the 7th harmonic of the controller output voltage
The harmonics controller corrects the power unit voltages so that the line-side current harmonics are reduced.
Dependency: Refer to: p3624, p3625
Description: Displays the voltage Vsd (active component) at the 3-phase line supply input of the power unit.
Description: Displays the voltage Vsq (reactive component) at the 3-phase line supply input of the power unit.
Description: Displays the angle of the input voltage (relative to the line angle).
Description: Sets the voltage scaler for the Voltage Sensing Module (VSM).
r3626[0...1] Infeed harmonics control output / INF harm_ctrl outp
A_INF Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: 5_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r3632 Infeed input voltage Vsd (active component) / INF V_inp Vsd
A_INF Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 1774, 8946,
8950
P-Group: Closed-loop control Units group: 5_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r3633 Infeed input voltage Vsq (reactive component) / INF V_inp Vsq
A_INF Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 1774, 8946,
8950
P-Group: Closed-loop control Units group: 5_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r3635 Infeed input voltage angle / INF V_inp angle
A_INF Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 8950
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [°] - [°] - [°]
p3660 VSM input line supply voltage, voltage scaler / VSM inp V_scaler
A_INF, S_INF Can be changed: T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9880
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 100000.00 [%] 0.00 [%]