Siemens SINAMICS S Series - r3575.0...2 BO: Master;slave DC link voltage monitoring status; Vdc monit status; r3602 Infeed control status; INF ctrl state; p3603 Infeed current pre-control factor D component; INF I_ctrl D�comp; r3606 Infeed active current controller system deviation; INF I_act ctrl dev

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-719
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the status of the DC link voltage monitoring for the master/slave.
Dependency: Refer to: r0088, p3510, p3574
Description: Displays the status of the closed-loop infeed control.
Values: 0: Initialization running
1: Pulse enable missing
2: Ramp-up, DC-link voltage
3: Ramp-up reactive current
4: Shutdown running
5: Reset identification
6: Operation
7: Identification running
8: Smart mode running
Description: The D component of the current pre-control is determined from the device data of the filter. p3603 can be used to
weigh the pre-calculated D component. If no dynamic pre-control is to be used, set the factor to zero.
Description: Displays the system deviation of the active current controller.
r3575.0...2 BO: Master/slave DC link voltage monitoring status / Vdc monit status
A_INF (Mas-
ter/Slave)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: 8948
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Upper limit value reached Yes No -
01 Lower limit value reached Yes No -
02 Upper/lower limit value reached Yes No -
r3602 Infeed control status / INF ctrl state
A_INF Can be changed: - Calculated: - Access level: 4
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0000 bin 1000 bin -
p3603 Infeed current pre-control factor D component / INF I_ctrl D-comp
A_INF Can be changed: U, T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: 8946
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 500.00 [%] 100.00 [%]
r3606 Infeed active current controller system deviation / INF I_act ctrl dev
A_INF Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 8946
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]