Parameters
List of parameters
1-692
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Proportional gain of the flux controller set from the motor identification.
Note: For synchronous motors, this parameters has no effect.
Description: Integral action time of the flux controller set from the motor identification.
Note: For synchronous motors, this parameters has no effect..
Description: Proportional gain of the current controller set from the motor identification.
Description: Integral action time of the current controller set from the motor identification.
Description: Sets the mode for the time stamp
p3100 = 0: Time stamp, operating hours
p3100 = 1: Time stamp, UTC format
p3080 Motor identification - flux controller P gain / MotId flux ctrl Kp
SERVO Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
0.0 [A/Vs] 999999.0 [A/Vs] 0.0 [A/Vs]
p3081 Motor identification - flux controller integral action time / MotId flux ctrl Tn
SERVO Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p3082 Motor identification - current controller P gain / MotId I_ctrl Kp
SERVO Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: 18_1 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.000 [V/A] 100000.000 [V/A] 0.000 [V/A]
p3083 Motor identification - current controller integral action time / MotId I_ctrl Tn
SERVO Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.00 [ms] 1000.00 [ms] 0.00 [ms]
p3100 RTC time stamp mode / RTC t_stamp mode
CU_CX32, CU_S Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1 0