PROFIdrive
Function Diagrams
2-1165
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-57 2453 – ZSW1 status word interconnection (p2038 = 1)
- 2453 -
Function diagram
8654321
fp_2453_01_eng.vsd
DO: SERVO
SINAMICS S
07.03.07 V02.05.00
PROFIdrive - ZSW1 status word interconnection (p2038 = 1)
Signal sources for ZSW1 in Interface Mode SIMODRIVE 611 universal (p2038 = 1)
<1> Used in telegrams 1, 2, 3, 4, 5, 6, 102, 103, 105, 106, 116, 352.
<2> The master system requests the process data.
7
<1>
-
Inverted
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
[2610]
[8060]
[2610]
[2610]
[2610]
[8065]
[8010]
[2503]
[8010]
-
-
-
[2522]
-
[2610]
[2610]
[Function diagram]
Signal source
p2080[2] = r0899.2
p2080[3] = r2139.3
p2080[4] = r0899.4
p2080[5] = r0899.5
p2080[6] = r0899.6
p2080[7] = r2139.7
p2080[8] = r2197.7
p2080[9] = r0899.9
p2080[10] = r2199.1
-
-
-
p2080[14] = r1407.2
-
p2080[0] = r0899.0
p2080[1] = r0899.1
Interconnection
parameters
[2503.7]
[2548.7]
[2503.7]
[2503.7]
[2503.7]
[2548.7]
[2534.7]
[2503.7]
[2536.7]
-
-
-
[2522.7]
-
[2503.7]
[2503.7]
[Function diagram]
Internal status word
ZSW1.0
ZSW1.1
ZSW1.2
ZSW1.3
ZSW1.4
ZSW1.5
ZSW1.6
ZSW1.8
ZSW1.9
ZSW1.11
ZSW1.12
ZSW1.13
ZSW1.14
ZSW1.15
ZSW1.7
ZSW1.10
Signal
1 = Ready to operate
1 = Ready to power-up
1 = Operation enabled
1 = Fault present
1 = No coast down active
1 = No fast stop active
1 = Power-on inhibit active
1 = Alarm present
1 = Speed setpoint - actual value deviation within tolerance t_off
1 = Control requested <2>
1 = f or n comparison value reached/exceeded
Reserved
Reserved
Reserved
Reserved
1 = Closed-loop torque control active
Meaning
Refer to [1020.7]
PROFIdrive sampling time