List of parameters
Parameters
1-67
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the actual speed of the closed-loop speed control and the V/f control.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Calculated from f_set - f_slip
Dependency: Refer to: r0021
Note: The speed actual value is calculated in sensorless operation and for V/f control. For operation with encoder, r0063
is smoothed with p1441.
The speed actual value r0063[0] is additionally displayed - smoothed with p0045 - in r0063[1].
The speed r0063[2] calculated from the output frequency and slip can only be compared with the speed actual
value r0063[0] in the steady-state.
Description: Displays the actual system deviation of the speed controller.
Note: In the servo control mode with active reference model, the system deviation to the P component of the speed/veloc-
ity controller is displayed.
Description: Displays the actual system deviation of the velocity controller.
Note: In the servo control mode with active reference model, the system deviation to the P component of the velocity con-
troller is displayed.
Description: Displays the slip frequency for induction motors (ASM).
r0063[0...2] CO: Actual speed value / n_ist
VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 1680, 4715
P-Group: Displays, signals Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [RPM] - [RPM] - [RPM]
r0064 CO: Speed controller system deviation / n_ctrl system dev
SERVO, VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 5040, 6040
P-Group: Displays, signals Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [RPM] - [RPM] - [RPM]
r0064 CO: Velocity controller system deviation / v_ctrl system dev
SERVO (Lin) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 5040, 6040
P-Group: Displays, signals Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [m/min] - [m/min] - [m/min]
r0065 Slip frequency / f_Slip
SERVO, VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 6310, 6730
P-Group: Displays, signals Units group: 2_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Hz] - [Hz] - [Hz]