SINAMICS S List Manual (LH1), 07/2007
In order that signal BO: r0873 is available at one of the infeeds, then BI: p0874 of the one infeed must be intercon-
nected to BO: r0863.0 of the other infeed.
Dependency: Refer to: r0863, p0874
Note: Mixed operation is not possible with the Active Line Module (ALM)!
Description: Setting to interconnect the ready signal for mixed operation of Smart Line Module (SLM) and Basic Line Module
(BLM).
In order that signal BO: r0873 is available at one of the infeeds, then BI: p0874 of the one infeed must be intercon-
nected to BO: r0863.0 of the other infeed.
Dependency: Refer to: r0863, r0873
Note: Mixed operation is not possible with the Active Line Module (ALM)!
Description: Sets the signal source to activate/de-activate a power unit component.
Dependency: BI: p0895 = 0 signal
De-activating power unit components
BI: p0895 = 1 signal
Activating power unit components
Refer to: p0125, r0126
Refer to: A05054
Note: The power unit is only de-activated when the pulses are canceled.
For units connected in parallel, when one of the power units is deactivated, then the enable in p7001 is withdrawn.
Description: Displays the status word for the "parking axis" function.
Dependency: Refer to: p0897
p0874 BI: Smart/ Basic Line Module operation / SLM/BLM operation
B_INF, S_INF Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 8732, 8832
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p0895[0...n] BI: Activate/de-activate power unit components / PU_comp act/de-act
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: PDS, p0120 Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1
r0896.0 BO: Parking axis, status word / Parking axis, ZSW
SERVO, VECTOR Can be changed: - Calculated: - Access level: 2
Data type: Unsigned8 Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Parking axis active Yes No -