Siemens SINAMICS S Series - p3701 APC enc sel; APC enc sel; p3704[0...n] APC filter activation; APC filter act; p3705[0...n] APC filter type; APC filter type; p3706[0...n] APC sub-sampling, filter 2.x; APC sub�samp. 2.x

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-734
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the number of the encoder used for for APC (Advanced Positioning Control).
Values: 2: Encoder 2
3: Encoder 3
Note: Encoder 1 is the motor encoder and cannot be used for APC as APC requires a load measuring system.
An encoder used for APC is, regarding its fault messages, treated just like a motor encoder - this means that its
fault messages are assigned to the drive.
Description: Setting to activate the filter for APC (Advanced Positioning Control).
Description: Sets the filter type for the filter for APC (Advanced Positioning Control).
Description: Sets the factor for the sub-sampling in the branch of filter 2.1 and 2.2 for APC (Advanced Positioning Control).
p3701 APC enc sel / APC enc sel
SERVO (APC) Can be changed: C1(4), U Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
2 3 2
p3704[0...n] APC filter activation / APC filter act
SERVO (APC) Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: DDS, p0180 Func. diagram: 7012
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Activating filter 1.1 Yes No -
04 Activating filter 2.1 Yes No -
05 Activating filter 2.2 Yes No -
08 Activating filter 3.1 Yes No -
09 Activating filter 3.2 Yes No -
p3705[0...n] APC filter type / APC filter type
SERVO (APC) Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: DDS, p0180 Func. diagram: 7012
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Filter 1.1 type A. Filter 2nd ord. Low pass (PT2) -
04 Filter 2.1 type A. Filter 2nd ord. Low pass (PT2) -
05 Filter 2.2 type A. Filter 2nd ord. Low pass (PT2) -
08 Filter 3.1 type A. Filter 2nd ord. Low pass (PT2) -
09 Filter 3.2 type A. Filter 2nd ord. Low pass (PT2) -
p3706[0...n] APC sub-sampling, filter 2.x / APC sub-samp. 2.x
SERVO (APC) Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: DDS, p0180 Func. diagram: 7012
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
1 64 1