List of parameters
Parameters
1-619
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the signal source for the minimum limiting of the technology controller.
Dependency: Refer to: p2292
Description: Displays the status word of the technology controller.
Description: Sets the signal source to select the "staging" function.
Description: Sets the assigned encoder.
The actual value preprocessing and the closed-loop position control are carried out using the assigned encoder.
Values: 0: No encoder
1: Encoder 1
2: Encoder 2
3: Encoder 3
Dependency: Refer to: p0187, p0188, p0189
Notice: For the setting p2502 = 0 (no encoder), closed-loop position control is not possible. This setting is only practical as
supportive measure to implement sensorless closed-loop speed control (e.g. if the motor encoder is defective).
p2298[0...n] CI: Technology controller minimum limiting / Tec_ctrl min_lim
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 2292[0]
r2349.0...3 CO/BO: Technology controller status word / Tec_ctrl stat word
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Technology controller de-activated Yes No -
01 Technology controller limited Yes No -
02 Technology controller, motorized potentiom-
eter limited max.
Yes No -
03 Technology controller, motorized potentiom-
eter limited min.
Yes No -
p2369 BI: Staging control word / Staging STW
VECTOR (Tech_ctrl) Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p2502[0...n] LR encoder assignment / Encoder assignment
SERVO (Pos ctrl),
VECTOR (Pos ctrl)
Can be changed: C2(25) Calculated: - Access level: 1
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: 4010
P-Group: Closed loop position control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 3 1