Faults and Alarms
List of faults and alarms
3-1458
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Notice:
Topology changes, that result in this fault being generated, cannot be accepted by the automatic function in the
device, but must be transferred using the commissioning software and parameter download. The automatic function
in the device only allows constant topology to be used. Otherwise, when the topology is changed, all of the previous
parameter settings are lost and replaced by the factory setting.
See also: r0098 (Actual device topology)
F01360 Topology: Actual topology is illegal
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The detected actual topology is not permissible.
Fault value (r0949, interpret hexadecimal):
Byte 1 (cause):
1: Too many components were detected at the Control Unit. The maximum permissible number of components is
199.
2: The component type of a component is not known. The preliminary component number is in the high word.
Note:
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy: Re fault value = 1:
Change the configuration. Connect less than 199 components to the Control Unit.
Re fault value = 2:
Remove the component with unknown component type.
A01361 Topology: Actual topology contains SINUMERIK and SIMOTION components
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The detected actual topology contains SINUMERIK and SIMOTION components.
Fault value (r0949, interpret hexadecimal):
Byte 1: Component number of the component.
Byte 2: Component class of the actual topology.
Byte 3 (cause):
1: An NX10 or NX15 was connected to a SIMOTION control.
2: A CX32 was connected to a SINUMERIK control.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy: Re fault value = 1:
Replace all NX10 or NX15 by a CX32.
Re fault value = 2:
Replace all CX32 by an NX10 or NX15.
F01375 Topology: Actual topology, duplicate connection between two components
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: When detecting the actual topology, a ring-type connection was detected.
Fault value (r0949, interpret hexadecimal):
Low word: Preliminary component number of a component included in the ring
Byte 3: Component class
Byte 4: Connection number
Example:
Fault value = 33751339 dec = 203012B hex
Byte 4 = 02 hex = 2 dec, byte 3 = 03 hex = 3 dec, low word = 012B hex = 299 dec
Component class:
1: Control unit
2: Motor Module
3: Line Module
4: Sensor Module (SM)
5: Voltage Sensing Module (VSM)
6: Terminal Module (TM)