List of parameters
Parameters
1-591
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the speed threshold value for the signal "|n_act| < speed threshold value 3" (BO: r2199.0).
Dependency: Refer to: p2150, r2199
Description: Sets the velocity threshold value for the signal "|v_act| < velocity threshold value 3" (BO: r2199.0).
Dependency: Refer to: p2150, r2199
Description: Sets the hysteresis speed (bandwidth) for the signal "n_act > n_max" (BO: r2197.6).
Dependency: Refer to: r1084, r1087, r2197
Notice: For p0322 = 0, the following applies: p2162 <= 0.1 * p0311
For p0322 > 0, the following applies: p1082 + p2162 <= 1.02 * p0322
If one of the conditions is violated, p2162 is appropriately and automatically reduced when exiting the commission-
ing mode.
Note: For a negative speed limit (r1087) the hysteresis is effective below the limit value and for a positive speed limit
(r1084) above the limit value.
Description: Sets the hysteresis velocity (bandwidth) for the signal "v_act > v_max" (BO: r2197.6).
Dependency: Refer to: r1084, r1087, r2197
p2161[0...n] Speed threshold 3 / n_thresh val 3
SERVO, VECTOR Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [RPM] 210000.00 [RPM] 5.00 [RPM]
p2161[0...n] Velocity threshold value 3 / v_thresh val 3
SERVO (Lin) Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [m/min] 1000.00 [m/min] 0.05 [m/min]
p2162[0...n] Hysteresis speed n_act > n_max / Hyst n_act>n_max
SERVO, VECTOR Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [RPM] 60000.00 [RPM] 0.00 [RPM]
p2162[0...n] Hysteresis velocity v_act > v_max / Hyst v_act>v_max
SERVO (Lin) Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [m/min] 1000.00 [m/min] 6.00 [m/min]