Description: Displays the last synchronization deviation that was determined.
r3108[0]: Milliseconds
r3108[1]: Days
Description: Sets the tolerance window for time synchronization.
When this tolerance window is exceeded, an appropriate alarm is output.
Dependency: Refer to: A01099
Description: Sets the delay time for external fault 3.
Dependency: Refer to: p2108, p3111, p3112
Refer to: F07862
Description: Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3112
Refer to: F07862
r3108[0...1] RTC last synchronization deviation / RTC sync_dev
CU_CX32, CU_S Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
p3109 RTC real time synchronization, tolerance window / RTC sync tol
CU_CX32, CU_S Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]
p3110 External fault 3, power-up delay / Ext fault 3 t_on
All objects Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 2546
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 0 [ms]
p3111 BI: External fault 3, enable / Ext fault 3 enab
CU_CX32, CU_LINK,
CU_S, DMC20,
TB30, TM15,
TM15DI_DO, TM17,
TM31, TM54F_MA,
TM54F_SL
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 2546
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1