Parameters
List of parameters
1-222
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: Refer to: p0728
Notice: To the terminal designation:
The first designation is valid for CU320, the second for CU310.
To select the values:
For CU310, CX32, NX10 and NX15, only DI/DO 9, 10, 11 can be selected as fast inputs (refer to the Equipment
Manual).
Note: Prerequisite: The DI/DO must be set as input (p0728.x = 0).
DI/DO: Bidirectional Digital Input/Output
If a parameter change is rejected, it should be checked as to whether the input terminal is already being used in
p0488, p0489, p0495, p0580, p2517 or p2518.
Description: Sets the signal source for the synchronizing signal (SYN) of the function "central measuring probe evaluation".
The signal is used to synchronize the common system time between the master and slave.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for the control word of the function "central measuring probe evaluation".
Description: Sets the evaluation technique for the function "central measuring probe evaluation".
Values: 0: Measurement with handshake
Description: Displays the control word for the function "central measuring probe evaluation".
p0681 BI: Central measuring probe, synchronizing signal signal source /
Cen meas sync_sig
CU_CX32, CU_S Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p0682 CI: Central measuring probe, control word signal source / Cen meas STW S_src
CU_CX32, CU_S Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Integer16 Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p0684 Central measuring probe evaluation technique / Cen meas eval
CU_CX32, CU_S Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 0 0
r0685 Central measuring probe, control word display / Cen meas STW disp
CU_CX32, CU_S Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -