List of parameters
Parameters
1-371
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Activates the V/f control with linear characteristic for diagnostic purposes.
0: Operation as set in p1300.
1: Activates the V/f control.
Values: 0: Off (p1300 eff)
1: On
Dependency: Refer to: p1318, p1319, p1326, p1327
Description: Sets the ramp-up and ramp-down time for the V/f control.
The ramp-function generator requires this time to reach the maximum speed (p1082) from zero.
Dependency: Refer to: p1317, p1319, p1326, p1327
Note: This ramp is used for stall protection and operates independently of any ramp-function generator that might have
been configured.
Description: The linear characteristic for the V/f control is defined by 0 Hz / p1319 and p1326 / p1327.
This parameter specifies the voltage for a frequency of 0 Hz.
Dependency: Activates the V/f control using p1317.
Refer to: p1317, p1326, p1327
Note: Linear interpolation is carried out between the points 0 Hz / p1319 and p1326 / p1327.
Description: The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the first point along the characteristic.
p1317[0...n] V/f control diagnostics activation / Uf diagn act
SERVO Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: 5718
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1 0
p1318[0...n] V/f control ramp-up/ramp-down time / Uf t_rmp-up_rmp-dn
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5300
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 999999.000 [s] 10.000 [s]
p1319[0...n] V/f control voltage at zero frequency / Uf V at f=0 Hz
SERVO Can be changed: U, T Calculated: CALC_MOD_REG Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5300
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [Vrms] 50.0 [Vrms] 0.0 [Vrms]
p1320[0...n] V/f control programmable characteristic frequency 1 / Uf char f1
VECTOR Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6300
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]