Siemens SINAMICS S Series - p1317[0...n] V;f control diagnostics activation; Uf diagn act; p1318[0...n] V;f control ramp-up;ramp-down time; Uf t_rmp�up_rmp�dn; p1319[0...n] V;f control voltage at zero frequency; Uf V at f=0 Hz; p1320[0...n] V;f control programmable characteristic frequency 1; Uf char f1

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-371
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Activates the V/f control with linear characteristic for diagnostic purposes.
0: Operation as set in p1300.
1: Activates the V/f control.
Values: 0: Off (p1300 eff)
1: On
Dependency: Refer to: p1318, p1319, p1326, p1327
Description: Sets the ramp-up and ramp-down time for the V/f control.
The ramp-function generator requires this time to reach the maximum speed (p1082) from zero.
Dependency: Refer to: p1317, p1319, p1326, p1327
Note: This ramp is used for stall protection and operates independently of any ramp-function generator that might have
been configured.
Description: The linear characteristic for the V/f control is defined by 0 Hz / p1319 and p1326 / p1327.
This parameter specifies the voltage for a frequency of 0 Hz.
Dependency: Activates the V/f control using p1317.
Refer to: p1317, p1326, p1327
Note: Linear interpolation is carried out between the points 0 Hz / p1319 and p1326 / p1327.
Description: The programmable characteristic for the V/f control is defined using 4 points and 0 Hz/p1310.
This parameter specifies the voltage of the first point along the characteristic.
p1317[0...n] V/f control diagnostics activation / Uf diagn act
SERVO Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: 5718
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1 0
p1318[0...n] V/f control ramp-up/ramp-down time / Uf t_rmp-up_rmp-dn
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5300
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 999999.000 [s] 10.000 [s]
p1319[0...n] V/f control voltage at zero frequency / Uf V at f=0 Hz
SERVO Can be changed: U, T Calculated: CALC_MOD_REG Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5300
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [Vrms] 50.0 [Vrms] 0.0 [Vrms]
p1320[0...n] V/f control programmable characteristic frequency 1 / Uf char f1
VECTOR Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6300
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]