Note: IF1: Interface 1
Description: Status display for the PROFIBUS interface.
Values: 0: Off
1: No connection (search for baud rate)
2: Connection O. K. (baud rate found)
3: Cyclic connection with master (data exchange)
4: Cyclic data O. K.
Note: Re r2054 = 3:
In state 3 (the LED flashes green), a cyclic connection has been established to the PROFIBUS master; however,
one of the following prerequisites is missing for cyclic operation:
- No setpoints are being received as the PROFIBUS master is in the STOP condition.
Only for clock-cycle synchronous operation, the following applies:
- The drive is not in synchronism as the global control (GC) has an error.
Re r2054 = 4:
In the status 4 (LED green), the cyclic connection to the PROFIBUS master has been established and setpoints are
being received. The clock cycle synchronization is OK, the global control (GC) is error-free.
This state does not provide any statement regarding the quality of the clock cycle synchronous sign-of-life charac-
ters on the drive objects.
Description: Status display for the internal communications interface.
Values: 0: No initialization
1: Fatal fault
2: Initialization
3: Send configuration
4: Receive configuration
5: Non-cyclic communication
6: Cyclic communications but no setpoints (stop/no clock cycle)
255: Cyclic communication
13 Bit 13 On Off -
14 Bit 14 On Off -
15 Bit 15 On Off -
r2054 PROFIBUS status / PB status
CU_S Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: 2410
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 4 -
r2054 COMM INT state / C INT state
CU_CX32, CU_LINK Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 255 -