Note: A change only becomes effective after a POWER ON.
SLS: Safely-Limited Speed / SG: Safely reduced speed
Description: Setting to select and de-select the acceptance test mode.
Values: 0: [00 hex] De-select the acceptance test mode
172: [AC hex] Select the acceptance test mode
Dependency: Refer to: p9558, r9571
Refer to: C01799
Description: Displays the status of the acceptance test mode.
Values: 0: [00 hex] Acc_mode inactive
12: [0C hex] Acc_mode not possible due to POWER ON fault
13: [0D hex] Acc_mode not possible due to incorrect ID in p9570
15: [0F hex] Acc_mode not possible due to expired Acc_timer
172: [AC hex] Acc_mode active
Dependency: Refer to: p9558, p9570
Refer to: C01799
Description: Sets the delay time after which the pulses are safely canceled after a bus failure.
Dependency: Refer to: p9561, p9563
Notice: The parameter is being prepared and is presently ineffective.
Note: A change only becomes effective after a POWER ON.
Description: Displays the Safety Integrated version for the safety motion monitoring functions on the Control Unit.
p9570 SI motion acceptance test mode (Control Unit) / SI Mtn Acc_mode
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0000 hex 00AC hex 0000 hex
r9571 SI motion acceptance test status (Control Unit) / SI Mtn acc_status
SERVO, VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0000 hex 00AC hex -
p9580 SI motion pulse cancelation delay time after bus failure (CU) / SI Mtn t to IL
SERVO, VECTOR Can be changed: C2 Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [ms] 800.00 [ms] 0.00 [ms]
r9590[0...2] SI motion version safety motion monitoring (Control Unit) / SI Mtn version
SERVO, VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -