Siemens SINAMICS S Series - p1094[0...n] Skip velocity 4; v_skip 4; p1101[0...n] Skip speed bandwidth; n_skip bandwidth; p1101[0...n] Skip velocity bandwidth; v_skip bandwidth

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-316
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets skip velocity 4.
Dependency: Refer to: p1091, p1092, p1093, p1101
Description: Sets the bandwidth for the skip speeds/velocities 1 to 4.
Dependency: Refer to: p1091, p1092, p1093, p1094
Note: The setpoint (reference) speeds are skipped (suppressed) in the range of the skip speed +/-p1101.
Steady-state operation is not possible in the skipped (suppressed) speed range. The skip (suppression) range is
skipped.
Example:
p1091 = 600 and p1101 = 20
--> setpoint speeds between 580 and 620 [rpm] are skipped.
For the skip bandwidths, the following hysteresis behavior applies:
For a setpoint speed coming from below, the following applies:
r1170 < 580 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 580 [rpm]
For a setpoint speed coming from above, the following applies:
r1170 > 620 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 620 [rpm]
Description: Sets the bandwidth for the skip velocities 1 to 4.
Dependency: Refer to: p1091, p1092, p1093, p1094
Note: The setpoint velocities are skipped (suppressed) in the range of the skip velocity +/-p1101.
Steady-state operation is not possible in the skipped (suppressed) velocity range. The skip (suppression) range is
skipped.
Example:
p1091 = 600 and p1101 = 20
--> setpoint velocities between 580 and 620 [rpm] are skipped.
For the skip bandwidths, the following hysteresis behavior applies:
For a setpoint velocity coming from below, the following applies:
r1170 < 580 [m/min] and 580 [m/min] <= r1114 <= 620 [m/min] --> r1119 = 580 [m/min]
For a setpoint velocity coming from above, the following applies:
r1170 > 620 [m/min] and 580 [m/min] <= r1114 <= 620 [m/min] --> r1119 = 620 [m/min]
p1094[0...n] Skip velocity 4 / v_skip 4
SERVO (Extended
setp, Lin)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [m/min] 1000.000 [m/min] 0.000 [m/min]
p1101[0...n] Skip speed bandwidth / n_skip bandwidth
SERVO (Extended
setp), VECTOR
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [RPM] 210000.000 [RPM] 0.000 [RPM]
p1101[0...n] Skip velocity bandwidth / v_skip bandwidth
SERVO (Extended
setp, Lin)
Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [m/min] 1000.000 [m/min] 0.000 [m/min]