Siemens SINAMICS S Series - r2198.4...12 CO;BO: Status word monitoring 2; ZSW monitor 2; r2199.0...11 CO;BO: Status word monitoring 3; ZSW monitor 3

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-604
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the second status word for monitoring functions.
Note: Re bit 10:
The force threshold value 1 is set in p2174.
Re bit 07:
For servo drives, bit 07 is not used and is always inactive.
Description: Displays the third status word for monitoring functions.
Note: Re bit 00:
The speed threshold value 3 is set in p2161.
Re bit 01:
The comparison value is set in p2141.
Re bit 11:
The torque threshold value 2 is set in p2194.
Description: Displays the third status word for monitoring functions.
r2198.4...12 CO/BO: Status word monitoring 2 / ZSW monitor 2
SERVO (Lin) Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2536
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
04 |n_set| < p2161 Yes No 8010
05 n_set > 0 Yes No 8010
06 Motor locked Yes No 8012
07 Motor stalled Yes No 8012
10 Force setpoint < force threshold value 1 Yes No 8012
11 Load monitoring signals an alarm Yes No 8013
12 Load monitoring signals a fault condition Yes No 8013
r2199.0...11 CO/BO: Status word monitoring 3 / ZSW monitor 3
SERVO, VECTOR Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2536
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| < speed threshold value 3 Yes No 8010
01 f or n comparison value reached or
exceeded
Yes No 8010
04 Speed setp - act val deviation in tolerance
t_on
Yes No 8010
05 Ramp-up/ramp-down completed Yes No 8010
06 Current below the zero current threshold Yes No -
11 Torque utilization < torque threshold value 2 Yes No 8012
r2199.0...11 CO/BO: Status word monitoring 3 / ZSW monitor 3
SERVO (Lin) Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2536
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -