Faults and Alarms
List of faults and alarms
3-1528
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Remedy: - check that the sensor is connected correctly.
- check the parameterization (p0600, p0601).
See also: r0035 (Temperature input), p0600 (Motor temperature sensor for monitoring), p0601 (Temperature sen-
sor, sensor type), p0607 (Temperature sensor fault timer)
F07016 Drive: Motor temperature sensor fault
Drive object: SERVO, VECTOR
Reaction: OFF1 (NONE, OFF2, OFF3, STOP1, STOP2)
Acknowledge: IMMEDIATELY
Cause: An error was detected when evaluating the temperature sensor set in p0600 and p0601.
Possible causes:
- wire breakage or sensor not connected (KTY: R > 1630 Ohm).
- measured resistance too low (PTC: R < 20 Ohm, KTY: R < 50 Ohm).
Note:
If alarm A07015 is present, the time in p0607 is started. If the fault is still present after this time has expired, then
fault F07016 is output; however, at the earliest, 1 s after alarm A07015.
Fault value (r0949, interpret decimal):
For SME selected (p0601 = 10), number of the sensor channel leading to the message.
See also: p0607 (Temperature sensor fault timer)
Remedy: - check that the sensor is connected correctly.
- check the parameterization (p0600, p0601).
- induction motors: De-activate temperature sensor fault (p0607 = 0).
See also: r0035 (Temperature input), p0600 (Motor temperature sensor for monitoring), p0601 (Temperature sen-
sor, sensor type), p0607 (Temperature sensor fault timer)
F07080 Drive: Incorrect control parameter
Drive object: A_INF, B_INF, SERVO, S_INF, VECTOR
Reaction: NONE
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The closed-loop control parameters have been parameterized incorrectly (e.g. p0356 = L_spread = 0).
Fault value (r0949, interpret decimal):
The fault value includes the parameter number involved.
The following parameter numbers only occur as fault values for vector drives:
p0310, for synchronous motors: p0341, p0344, p0350, p0357
The following parameter numbers do not occur as fault values for synchronous motors:
p0354, p0358, p0360
See also: p0310 (Rated motor frequency), p0311 (Rated motor speed), p0341 (Motor moment of inertia), p0344
(Motor weight), p0350 (Motor stator resistance, cold), p0354 (Motor rotor resistance cold / damping resistance d
axis), p0356 (Motor stator leakage inductance), p0357 (Motor stator inductance, d axis), p0358 (Motor rotor leakage
inductance / damping inductance, d axis), p0360 (Motor magnetizing inductance/magn. inductance, d axis satu-
rated), p0400 (Enc type selection), p0640 (Current limit), p1082 (Maximum speed), p1300 (Open-loop/closed-loop
control operating mode)
Remedy: Modify the parameter indicated in the fault value (r0949) (e.g. p0640 = current limit > 0).
See also: p0311 (Rated motor speed), p0341 (Motor moment of inertia), p0344 (Motor weight), p0350 (Motor stator
resistance, cold), p0354 (Motor rotor resistance cold / damping resistance d axis), p0356 (Motor stator leakage
inductance), p0358 (Motor rotor leakage inductance / damping inductance, d axis), p0360 (Motor magnetizing induc-
tance/magn. inductance, d axis saturated), p0400 (Enc type selection), p0640 (Current limit), p1082 (Maximum
speed)
F07082 Macro: Execution not possible
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The macro cannot be executed.
Fault value (r0949, interpret hexadecimal):
The fault code is in byte 1, possibly supplementary information is in byte 2 and the high word contains the parameter
number involved if this is available.
Fault codes:
Fault for the trigger parameter itself:
-20: Called file is not valid for parameter 15.