List of faults and alarms
Faults and Alarms
3-1473
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Remedy: None necessary.
Reaction upon F: NONE
Acknowl. upon F: IMMEDIATELY
F01515 (A) BICO: Writing to parameter not permitted as the master control is active
Drive object: A_INF, B_INF, SERVO, S_INF, VECTOR
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: While changing the number of CDS or when copying from CDS, the master control was active.
Remedy: None necessary.
Reaction upon A: NONE
Acknowl. upon A: NONE
A01590 (F) Drive: Motor maintenance interval expired
Drive object: A_INF, B_INF, CU_LINK, DMC20, SERVO, S_INF, TB30, TM15, TM15DI_DO, TM17, TM31, TM41, TM54F_MA,
TM54F_SL, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The selected service/maintenance interval for this motor was reached.
Alarm value (r2124, interpret decimal):
Motor data set number.
See also: p0650 (Actual motor operating hours), p0651 (Motor operating hours maintenance interval)
Remedy: carry out service/maintenance and reset the service/maintenance interval (p0651).
Reaction upon F: NONE
Acknowl. upon F: IMMEDIATELY
F01600 SI CU: STOP A initiated
Drive object: SERVO, VECTOR
Reaction: OFF2
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The drive-based "Safety Integrated" function in the Control Unit (CU) has detected a fault and initiated a STOP A
(pulse cancelation via the safety shutdown path of the Control Unit).
- forced checking procedure of the safety shutdown path of the Control Unit unsuccessful.
- subsequent response to fault F01611 (defect in a monitoring channel).
Fault value (r0949, interpret decimal):
0: Stop request from the Motor Module.
1005: Pulses canceled although STO not selected and there is no internal STOP A present.
1010: Pulses enabled although STO is selected or an internal STOP A is present.
1015: Feedback of the safe pulse cancelation for Motor Modules connected in parallel are different.
9999: Subsequent response to fault F01611.
Remedy: - select Safe Torque Off and de-select again.
- replace the Motor Module involved.
Re fault value = 9999:
- carry out diagnostics for fault F01611.
Note:
CU: Control Unit
MM: Motor Module
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill