Parameters
List of parameters
1-434
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the signal source for the scaling of the upper or motoring force limit in p1522.
Dependency: p1400 bit 4 = 0: Upper / lower
p1400 bit 4 = 1: Motoring / generating
Danger: For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Negative values. that are obtained as a result of the signal source and the scaling can cause the motor to acceler-
ate in an uncontrollable fashion.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for the scaling of the upper torque limit in p1522.
Danger: For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Negative values. that are obtained as a result of the signal source and the scaling can cause the motor to acceler-
ate in an uncontrollable fashion.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for the scaling of the lower torque limit or the regenerative torque limit in p1523.
Dependency: p1400 bit 4 = 0: Upper / lower
p1400 bit 4 = 1: Motoring / generating
Danger: For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values. that are obtained as a result of the signal source and the scaling can cause the motor to accelerate
in an uncontrollable fashion.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1528[0...n] CI: Force limit upper/motoring scaling / F_max up/mot scal
SERVO (Lin) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 1610, 3617,
5620, 5630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 1524[0]
p1528[0...n] CI: Torque limit upper scaling / M_max upper scal
VECTOR (n/M) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 6630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 1524[0]
p1529[0...n] CI: Torque limit lower/regenerating scaling / M_max low/gen scal
SERVO Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 1610, 3617,
5620, 5630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 1525[0]