Parameters
List of parameters
1-66
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the actual velocity setpoint after the setpoint filters.
Description: Displays the actual, smoothed actual speed for speed control.
Dependency: Refer to: r0021
Note: The speed actual value is calculated in sensorless operation. For operation with encoder, r0063 is smoothed with
p1441.
The speed actual value is available smoothed (r0021) and unsmoothed (r0063).
Description: Displays the actual, smoothed velocity actual value for velocity control.
Dependency: Refer to: r0021
Note: The velocity actual value is calculated in sensorless operation. For operation with encoder, r0063 is smoothed with
p1441.
The velocity actual value is available smoothed (r0021) and unsmoothed (r0063).
Description: Displays the currently smoothed speed actual value.
Note: For Terminal Module 41 (TM41), this value is used to interconnect with standard telegram 3 and is always zero.
r0062 CO: Velocity setpoint after the filter / v_set after filter
SERVO (Lin) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 1590, 1750,
5020, 5030, 5210, 6030
P-Group: Displays, signals Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [m/min] - [m/min] - [m/min]
r0063 CO: Speed actual value after actual value smoothing / n_ist smooth
SERVO Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 1580, 1590,
4710, 5300
P-Group: Displays, signals Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [RPM] - [RPM] - [RPM]
r0063 CO: Actual velocity smoothed / v_act smooth
SERVO (Lin) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 1580, 1590,
4710, 5300
P-Group: Displays, signals Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [m/min] - [m/min] - [m/min]
r0063 CO: Speed actual value after actual value smoothing / n_ist smooth
TM41 Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [RPM] - [RPM] - [RPM]