List of parameters
Parameters
1-979
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the limit values for the function "Safely-Limited Speed" (SLS).
Index: [0] = Limit value SLS1
[1] = Limit value SLS2
[2] = Limit value SLS3
[3] = Limit value SLP4
Dependency: Refer to: p9363, p9531
Refer to: C01714
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
SLS: Safely-Limited Speed
Description: Sets the tolerance for the cross-check of the actual position between the two monitoring channels.
Dependency: Refer to: p9542
Refer to: C01711
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
Description: Sets the tolerance for the cross-check of the actual position between the two monitoring channels.
Dependency: Refer to: p9542
Refer to: C01711
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
p9331[0...3] SI motion SLS limit values (Motor Module) / SI Mtn SLS lim MM
SERVO (Safety rot),
VECTOR (Safety rot)
Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [RPM] 1000000.00 [RPM] 2000.00 [RPM]
p9342 SI motion act val comparison tol (crosswise) (Motor Module) / SI Mtn act tol MM
SERVO, VECTOR Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0010 [mm] 360.0000 [mm] 0.1000 [mm]
p9342 SI motion act val comparison tol (crosswise) (Motor Module) / SI Mtn act tol MM
SERVO (Safety rot),
VECTOR (Safety rot)
Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0010 [°] 360.0000 [°] 0.1000 [°]