Siemens SINAMICS S Series - p1676[0...n] Current setpoint filter 4 numerator damping; I_set_filt 4 D_z; p1699 Filter data acceptance; Filt data accept; p1701[0...n] Current controller reference model dead time; I_ctrRefMod t_dead; p1702[0...n] Isd current controller pre-control scaling; Isd_ctr_prectrScal

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-467
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the numerator damping for current setpoint filter 4.
Dependency: The current setpoint filters are parameterized with p1656 to p1676.
Description: Activates data acceptance for parameter changes for the filter.
p1699 = 0:
The new filter data are immediately accepted.
p1699 = 1:
The new filter data are only accepted when this parameter is reset.
Dependency: Refer to: p1414, p1415, p1416, p1417, p1418, p1419, p1420, p1421, p1422, p1423, p1424, p1425, p1426, p1656,
p1657, p1658, p1659, p1660, p1661, p1662, p1663, p1664, p1665, p1666, p1667, p1668, p1669, p1670, p1671,
p1672, p1673, p1674, p1675, p1676
Description: Sets the fractional dead time for the current controller reference model.
This parameter emulates the computation dead time of the proportionally controlled current control loop.
Note: Dead time = p1701 * p0115[0]
Description: Sets the scaling of the dynamic current controller pre-control for the flux-generating current component Isd.
Note: The parameter is effective for permanent and separately-excited synchronous motors.
p1676[0...n] Current setpoint filter 4 numerator damping / I_set_filt 4 D_z
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5710
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 10.000 0.700
p1699 Filter data acceptance / Filt data accept
SERVO, VECTOR
(n/M)
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0 1 0
p1701[0...n] Current controller reference model dead time / I_ctrRefMod t_dead
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5714
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 1.0 1.0
p1702[0...n] Isd current controller pre-control scaling / Isd_ctr_prectrScal
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6714
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, REL Expert list: 1
Min Max Factory setting
0.0 [%] 200.0 [%] 70.0 [%]