List of parameters
Parameters
1-467
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the numerator damping for current setpoint filter 4.
Dependency: The current setpoint filters are parameterized with p1656 to p1676.
Description: Activates data acceptance for parameter changes for the filter.
p1699 = 0:
The new filter data are immediately accepted.
p1699 = 1:
The new filter data are only accepted when this parameter is reset.
Dependency: Refer to: p1414, p1415, p1416, p1417, p1418, p1419, p1420, p1421, p1422, p1423, p1424, p1425, p1426, p1656,
p1657, p1658, p1659, p1660, p1661, p1662, p1663, p1664, p1665, p1666, p1667, p1668, p1669, p1670, p1671,
p1672, p1673, p1674, p1675, p1676
Description: Sets the fractional dead time for the current controller reference model.
This parameter emulates the computation dead time of the proportionally controlled current control loop.
Note: Dead time = p1701 * p0115[0]
Description: Sets the scaling of the dynamic current controller pre-control for the flux-generating current component Isd.
Note: The parameter is effective for permanent and separately-excited synchronous motors.
p1676[0...n] Current setpoint filter 4 numerator damping / I_set_filt 4 D_z
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5710
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 10.000 0.700
p1699 Filter data acceptance / Filt data accept
SERVO, VECTOR
(n/M)
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0 1 0
p1701[0...n] Current controller reference model dead time / I_ctrRefMod t_dead
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5714
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 1.0 1.0
p1702[0...n] Isd current controller pre-control scaling / Isd_ctr_prectrScal
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6714
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, REL Expert list: 1
Min Max Factory setting
0.0 [%] 200.0 [%] 70.0 [%]