List of parameters
Parameters
1-701
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note: Re bit 02:
When phase failure is detected the bit is set and alarm A06205 is output.
The bit is reset for the following events:
- the infeed had reached the normal operating state again after a phase failure has been bypassed/buffered (p3402
= 9).
- the pulse enable is withdrawn due to a fault or powering-down with OFF1/OFF2.
Description: Displays the status word of the infeed.
Description: Sets the mode to detect the line supply frequency.
Values: 0: Line supply frequency setting 50/60 Hz off
1: Line supply frequency setting 50/60 Hz on
Dependency: Refer to: p0211, p0284, p0285
Refer to: A06350, A06351, F06500
Note: For p3409 = 1, the following applies:
After operation has been enabled, the rated line supply frequency (p0211) is automatically set to a value of 50 Hz or
60 Hz corresponding to the currently measured frequency. This means that the parameter value of p0211 is, under
certain circumstances, changed.
For p3409 = 0, the following applies:
The system does not change parameter p0211.
Description: Sets the line and DC link parameter identification routine for the infeed module.
Values: 0: Identification (Id) off
1: Activate identification (Id)
2: Set controller settings
3: Save identification and controller settings
4: Save identification and controller settings with L adaptation
5: Reset, save Id and controller setting with L adaptation
r3405.7 CO/BO: Status word infeed / INF ZSW
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
07 DC link undervoltage alarm threshold fallen
below
Yes No -
p3409 Infeed line frequency setting / INF f_line_mode
A_INF, S_INF Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1 1
p3410 Infeed identification method / INF Ident_type
A_INF, S_INF Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 5 5