Siemens SINAMICS S Series - p10003 SI forced checking procedure timer; SI FrcdCkProcTimer; r10004[0...1] SI actual checksum TM54 F parameters; SI act CRC TM54 F; p10005[0...1] SI reference checksum TM54 F parameters; SI ref CRC TM54 F; p10006 SI acknowledgement internal event input terminal; SI ackn int event

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-1049
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the time to carry out the forced checking procedure (test stop).
Within the parameterized time, the digital inputs/outputs must must have been subject to a forced checking proce-
dure at least once. The forced checking procedure is started with BI: p10007 = 0/1 signal.
Dependency: Refer to: p10001, p10007, p10046
Description: Displays the actual checksum of the checksum-checked parameters for the Terminal Module 54F (TM54F).
Description: Displays the reference checksum of the checksum-checked parameters for the Terminal Module 54F (TM54F).
Description: Select a safety-relevant digital input for the signal "acknowledge internal event" (internal fault).
The signal is transferred to the corresponding control signal of all drives. The falling edge at this input resets the
status "internal event" in the drives.
Values: 0: Statically active
1: F-DI 0 (X521.2/3/6)
2: F-DI 1 (X521.4/5/7)
3: F-DI 2 (X522.1/2/7)
4: F-DI 3 (X522.3/4/8)
5: F-DI 4 (X522.5/6/9)
6: F-DI 5 (X531.2/3/6)
7: F-DI 6 (X531.4/5/7)
8: F-DI 7 (X532.1/2/7)
9: F-DI 8 (X532.3/4/8)
10: F-DI 9 (X532.5/6/9)
255: Statically inact
p10003 SI forced checking procedure timer / SI FrcdCkProcTimer
TM54F_MA Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 2848
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [h] 8760.00 [h] 8.00 [h]
r10004[0...1] SI actual checksum TM54F parameters / SI act CRC TM54F
TM54F_MA,
TM54F_SL
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: 2846
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
p10005[0...1] SI reference checksum TM54F parameters / SI ref CRC TM54F
TM54F_MA,
TM54F_SL
Can be changed: C2 Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: 2846
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
p10006 SI acknowledgement internal event input terminal / SI ackn int event
TM54F_MA,
TM54F_SL
Can be changed: C2 Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 255 0