Description: Sets the normalization characteristic for the analog outputs of terminal module 31 (TM31).
The normalization characteristic for the analog outputs is defined using 2 points.
This parameter specifies the y coordinate (output voltage in V or output current in mA) of the 2nd value pair of the
characteristic.
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency: The units of this parameter (V or mA) depend on the analog input type.
Refer to: r4076, p4076
Notice: This parameter is automatically overwritten when the analog output type is changed (p4076).
Note: This parameter is overwritten if p4076 (type of analog output) is changed.
The parameters for the characteristic do not limit.
Description: Sets the signal source for inverting the analog output signals of the Terminal Board 30 (TB30).
Index: [0] = AO 0 (X482.5/X482.6)
[1] = AO 1 (X482.7/X482.8)
Description: Sets the signal source to invert the analog output signals of terminal module 31 (TM31).
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Description: Sets the offset for the analog outputs of Terminal Board 30 (TB30).
The offset is added to the output signal after the normalization characteristic.
p4080[0...1] TM31 analog outputs, characteristic value y2 / TM31 AO char y2
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 9572
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-20.000 [V] 20.000 [V] 10.000 [V]
p4082[0...1] BI: TB30 analog outputs, signal source for inversion / TB30 AO invert
TB30 Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 9106
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p4082[0...1] BI: TM31 analog outputs, signal source for inversion / TM31 AO invert
TM31 Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 9572
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p4083[0...1] TB30 analog outputs, offset / TB30 AO offset
TB30 Can be changed: U, T Calculated: - Access level: 1
Data type: Floating Point Dynamic index: - Func. diagram: 9106
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-10.000 10.000 0.000