Parameters
List of parameters
1-368
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the response for the Vdc_min controller (kinetic buffering).
Values: 0: Buffer Vdc until undervoltage, n<p1297 -> F07405
1: Buff. Vdc until undervolt., n<p1297 -> F07405, t>p1295 -> F07406
Description: Sets the speed threshold for the Vdc-min controller (kinetic buffering). If this value is exceeded a fault is output; the
required response can be parameterized .
Description: Displays the actual output of the Vdc controller (DC link voltage controller)
Description: Sets the open and closed loop control mode of a drive.
Values: 20: Speed control (sensorless)
21: Speed control (with encoder)
23: Torque control (with encoder)
Dependency: Closed-loop speed or torque control (with encoder) cannot be selected if the encoder type is not entered (p0400).
Refer to: p0108, r0108, p0300, p0311, p0400, p1501
Note: The closed-loop torque control can only be changed over in operation (p1300 = 20, 21) by selecting the closed-loop
speed control (p1501). At the changeover, the setting of p1300 does not change. In this case, the actual state is dis-
played in r1407, bit 2 and bit 3.
For sensorless operation (p1404 = 0 or p1300 = 20), the following applies:
- The following condition must be fulfilled: p1800 >= n / (2 * p0115[0]), n = 1, 2, ...
- For motors with a small power rating (< 300 W) we recommend to set n >= 2.
p1296[0...n] Vdc_min controller response (kinetic buffering) (V/f / Vdc_min response
VECTOR Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1 0
p1297[0...n] Vdc_min controller speed threshold (V/f) / Vdc_min n_thresh
VECTOR Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Functions Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [RPM] 210000.0 [RPM] 50.0 [RPM]
r1298 CO: Vdc controller output (V/f) / Vdc_ctrl output
VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 6320
P-Group: Functions Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [RPM] - [RPM] - [RPM]
p1300[0...n] Open-loop/closed-loop control operating mode / Op/cl-lp ctrl_mode
SERVO Can be changed: C2(1), T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: 1590, 1690,
5060, 6300
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
20 23 21