Description: Sets the final rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the smoothed response to the OFF1 command or the reduced setpoint for the extended ramp-function gener-
ator.
Values: 0: Cont. smoothing
1: Discont smoothing
Dependency: No effect up to initial rounding-off time (p1130) > 0 s.
Note: p1134 = 0 (continuous smoothing)
If the setpoint is reduced while ramping-up, initially a final rounding-off is carried out and then the ramp-up com-
pleted. During the final rounding-off, the output of the ramp-function generator continues to go in the direction of the
previous setpoint (overshoot). After the final rounding-off has been completed, the output goes toward the new set-
point.
p1134 = 1 (discontinuous smoothing)
If the setpoint is reduced while ramping-up, then the output goes immediately in the direction of the new setpoint.
For the setpoint change there is no rounding-off.
Description: Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Note: This time can be exceeded if the DC-link voltage reaches its maximum value.
Description: Sets the ramp-down time from the maximum velocity down to zero speed for the OFF3 command.
Note: This time can be exceeded if the DC-link voltage reaches its maximum value.
p1131[0...n] Ramp-function generator final rounding-off time / RFG t_end_delay
SERVO (Extended
setp), VECTOR
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1134[0...n] Ramp-function generator rounding-off type / RFG round-off type
SERVO (Extended
setp), VECTOR
Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1 0
p1135[0...n] OFF3 ramp-down time / RFG OFF3 t_ramp-dn
SERVO Can be changed: C2(1), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3060, 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 600.000 [s] 0.000 [s]
p1135[0...n] OFF3 ramp-down time / RFG OFF3 t_ramp-dn
SERVO (Lin) Can be changed: C2(1), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3060, 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 600.000 [s] 0.000 [s]