EasyManua.ls Logo

Siemens SINAMICS S Series - A30073 (N) Actual value;setpoint preprocessing no longer synchronous to DRIVE-CLiQ; F30074 Communications error to the power unit module; F30105 PU: Actual value sensing fault; F30600 SI MM: STOP A initiated

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Faults and Alarms
List of faults and alarms
3-1620
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A30073 (N) Actual value/setpoint preprocessing no longer synchronous to DRIVE-CLiQ
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The following applies for CU31x and CUA31:
Communications to the power unit module are no longer in synchronism with DRIVE-CLiQ.
Remedy: The following applies for CU31x and CUA31:
Wait until synchronization is re-established.
Reaction upon N: NONE
Acknowl. upon N: NONE
F30074 Communications error to the power unit module
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: Communications is not possible to the power unit via the plug contact.
Remedy: The following applies for CU31x and CUA31:
Either replace the CU board or the power unit. You must check which of the two components must be replaced by
replacing one and then the other component; if neither are available then both components must be returned.
F30105 PU: Actual value sensing fault
Drive object: All objects
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: At least one incorrect actual value channel was detected on the Power Stack Adapter (PSA).
The incorrect actual value channels are displayed in the following diagnostic parameters.
Remedy: Evaluate the diagnostic parameters.
If the actual value channel is incorrect, check the components and if required, replace.
F30600 SI MM: STOP A initiated
Drive object: All objects
Reaction: OFF2
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The drive-based "Safety Integrated" function in the Motor Module (MM) has detected a fault and initiated STOP A
(pulse cancelation via the safety shutdown path of the Motor Module).
- forced checking procedure of the safety shutdown path of the Motor Module unsuccessful.
- subsequent response to fault F30611 (defect in a monitoring channel).
Fault value (r0949, interpret decimal):
0: Stop request from the Control Unit.
1005: Pulses canceled although STO not selected and there is no internal STOP A present.
1010: Pulses enabled although STO is selected or an internal STOP A is present.
9999: Subsequent response to fault F30611.
Remedy: - select Safe Torque Off and de-select again.
- replace the Motor Module involved.
Re fault value = 9999:
- carry out diagnostics for fault F30611.
Note:
CU: Control Unit
MM: Motor Module
SI: Safety Integrated
STO: Safe Torque Off / SH: Safe standstill