Faults and Alarms
List of faults and alarms
3-1442
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Remedy: - save the parameters (p0971/p0977).
- carry out a POWER ON (power off/on) for all components.
F01041 Parameter save necessary
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: Defective or missing files were detected on the CompactFlash card when booting.
Fault value (r0949, interpret decimal):
-1: Source file cannot be opened.
-2: Source file cannot be read.
-3: Target directory cannot be set-up.
-4: Target file cannot be set-up/opened.
-5: Target file cannot be written into.
Additional values:
Only for internal Siemens troubleshooting.
Remedy: - save the parameters (p0977).
- download the project again into the drive unit.
- update the firmware
- if required, replace the Control Unit and/or CompactFlash card.
F01042 Parameter error for a project download
Drive object: All objects
Reaction: A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (NONE, OFF1, OFF3)
VECTOR: OFF2 (NONE, OFF1, OFF3)
Acknowledge: IMMEDIATELY
Cause: An error was detected when downloading a project using the commissioning (start-up) software (e.g. incorrect
parameter value).
For the specified parameter, it was detected that dynamic limits were exceeded that could possibly depend on other
parameters.
Fault value (r0949, interpret decimal):
Low word: Parameter number (16 bits without sign)
Byte 3: Parameter index
Byte 4: Error ID
0: Parameter number illegal.
1: Parameter value cannot be changed.
2: Lower or upper value limit exceeded.
3: Sub-index incorrect.
4: No array, no sub-index.
5: Data type incorrect.
6: Setting not permitted (only resetting).
7: Descriptive element cannot be changed.
9: Descriptive data not available.
11: No master control.
15: No text array present.
17: Task cannot be executed due to operating status.
20: Illegal value.
21: Response too long.
22: Parameter address illegal.
23: Format illegal.
24: Number of values not consistent.
25: Drive object does not exist.
101: Presently de-activated.
104: Illegal value.
107: Write access not permitted when controller enabled.
108: Units unknown.
109: Write access only in the commissioning state, encoder (p0010 = 4).
110: Write access only in the commissioning state, motor (p0010 = 3).
111: Write access only in the commissioning state, power unit (p0010 = 2).
112: Write access only in the quick commissioning mode (p0010 = 1).