Description: Sets the response for the Vdc_min controller (kinetic buffering).
Values: 0: Buffer Vdc until undervoltage, n<p1257 -> F07405
1: Buff. Vdc until undervolt., n<p1257 -> F07405, t>p1255 -> F07406
Dependency: Refer to: F07405, F07406
Description: Sets the speed threshold for the Vdc-min controller (kinetic buffering). If this value is exceeded a fault is output; the
required response can be parameterized .
Description: Displays the actual output of the Vdc controller (DC link voltage controller)
Note: The regenerative power limit p1531 is used for vector control to pre-control the Vdc_max controller. The lower the
power limit is set, the lower the correction signals of the controller when the voltage limit is reached.
Description: Selecting the bypass functionality.
Values: 0: Bypass function de-activated
1: Bypass with synchronization and overlap
2: Bypass with synchronization without overlap
3: Bypass without synchronization
Dependency: The bypass functionality is enabled together with the function module "technology controller (r0108.16).
For p1260 = 2 (bypass with synchronization without overlap) and p1260 = 3 (bypass without synchronization), then
the "flying restart" function must be activated (p1200).
p1256[0...n] Vdc_min controller response (kinetic buffering) / Vdc_min response
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0 1 0
p1257[0...n] Vdc_min controller speed threshold / Vdc_min n_thresh
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Functions Units group: 3_1 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.0 [RPM] 210000.0 [RPM] 50.0 [RPM]
r1258 CO: Vdc controller output / Vdc_ctrl output
VECTOR (n/M) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 6220
P-Group: Functions Units group: 6_2 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p1260 Bypass configuration / Bypass config
VECTOR (Tech_ctrl) Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 3 0