List of parameters
Parameters
1-247
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the Command Data Set (CDS) selected using p0810 ... p0813.
Dependency: Refer to: r0050, p0810, p0811
Note: The currently effective command data set is displayed in r0050.
Description: Displays the Drive Data Set (DDS) selected using p0820 ... p0824.
Dependency: Refer to: r0051, p0820, p0821, p0822, p0823, p0824
Note: If there is only one data set, then a value of 0 is displayed in this parameter and not the selection via binector inputs.
Description: Displays the selected Motor Data Set (MDS) and the selected Encoder Data Sets (EDS).
Index: [0] = Motor Data Set MDS selected
[1] = Encoder 1 Encoder Data Set EDS selected
[2] = Encoder 2 Encoder Data Set EDS selected
[3] = Encoder 3 Encoder Data Set EDS selected
Dependency: Refer to: r0049, p0186, p0187, p0188, p0189
Note: Value 99 means the following: No encoder assigned (not configured).
r0836.0...3 CO/BO: Command Data Set CDS selected / CDS selected
A_INF, B_INF,
SERVO, S_INF,
TM41, VECTOR
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned8 Dynamic index: - Func. diagram: 1530, 8560
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 CDS select. bit 0 On Off -
01 CDS select. bit 1 On Off -
02 CDS select. bit 2 On Off -
03 CDS select. bit 3 On Off -
r0837.0...4 CO/BO: Drive Data Set DDS selected / DDS selected
SERVO, TM41, VEC-
TOR
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned8 Dynamic index: - Func. diagram: 8565
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DDS select. bit 0 On Off -
01 DDS select. bit 1 On Off -
02 DDS select. bit 2 On Off -
03 DDS select. bit 3 On Off -
04 DDS select. bit 4 On Off -
r0838[0...3] Motor/encoder data set selected / MDS/EDS selected
SERVO, VECTOR Can be changed: - Calculated: - Access level: 2
Data type: Unsigned8 Dynamic index: - Func. diagram: 8565
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -