Function Diagrams
PROFIdrive
2-1166
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-58 2454 – ZSW2 status word interconnection (p2038 = 0)
- 2454 -
Function diagram
87654321
fp_2454_01_eng.vsd
DO: SERVO, VECTOR
SINAMICS S
08.05.07 V02.05.00
PROFIdrive - ZSW2 status word interconnection (p2038 = 0)
<2>
<1> Used in telegrams 2, 3, 4, 5, 6, 7, 110.
<2> These signals are automatically interconnected for clock-cycle synchronous operation.
[Function diagram]
signal source
Interconnection
parameters
Signal Meaning
p2081[2] = r0051.2
p2081[3] = r0051.3
p2081[4] = r0051.4
-
-
p2081[7] = r0896.0
p2081[8] = r1406.8
-
-
p2081[11] = r0835.0
Implicitly interconnected
Implicitly interconnected
Implicitly interconnected
Implicitly interconnected
p2081[0] = r0051.0
p2081[1] = r0051.1
ZSW2.0
ZSW2.1
ZSW2.2
ZSW2.3
ZSW2.4
ZSW2.5
ZSW2.6
ZSW2.8
ZSW2.9
ZSW2.11
ZSW2.12
ZSW2.13
ZSW2.14
ZSW2.15
ZSW2.7
ZSW2.10
1 = Drive data set DDS effective, bit 0
1 = Drive data set DDS effective, bit 1
1 = Drive data set DDS effective, bit 2
1 = Drive data set DDS effective, bit 3
1 = Drive data set DDS effective, bit 4
Reserved
Reserved
1 = Parking axis active
1 = Traverse to fixed endstop
Reserved
Reserved
1 = Data set changeover active
Slave sign-of-life bit 0
Slave sign-of-life bit 1
Slave sign-of-life bit 3
Slave sign-of-life bit 2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
[Function diagram]
internal status word
[8565]
[8565]
[8565]
-
-
-
[2520]
-
-
-
-
-
-
-
[8565]
[8565]
Signal sources for ZSW2 in Interface Mode SINAMICS (p2038 = 0)
<1>
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Inverted
Refer to [1020.7]
PROFIdrive sampling time