List of parameters
Parameters
1-515
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
The percentage value is referred to p0310 (rated motor frequency).
Synchronous motor:
The percentage value is referred to the minimum from p0310 (rated motor frequency) and p1082 (maximum
speed).
Dependency: Refer to: p0310, p1959
Refer to: F07984, F07985
Note: In order to calculate the inertia, sudden speed changes are carried out - the specified value corresponds to the
lower speed setpoint. This value is increased by 20 % for the upper speed value. The q leakage inductance (refer to
p1959 bit 5) is determined at zero speed and at 50% of p1965 - however, with a maximum output frequency of 15
Hz and at a minimum of 10% of the rated motor speed.
Description: Sets the dynamic response factor for speed controller optimization.
Dependency: Refer to: p1959
Refer to: F07985
Note: For a rotating measurement, this parameter can be used to optimize the speed controller.
p1967 = 100 % --> speed controller optimization according to a symmetric optimum.
p1967 > 100 % --> optimization with a higher dynamic response (Kp higher, Tn lower).
Description: Displays the dynamic factor which is actually achieved for the vibration test
Dependency: Refer to: p1959, p1967
Refer to: F07985
Note: This dynamics factor only refers to the control mode of the speed controller set in p1960.
Description: Displays the identified moment of inertia.
Dependency: Refer to: p0341, p0342, p1498, p1959, p1960
p1967 Speed_ctrl_opt dynamic factor / n_opt dyn_factor
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
1 [%] 400 [%] 100 [%]
r1968 Speed_ctrl_opt dynamic factor actual / n_opt dyn_fact act
VECTOR (n/M) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r1969 Moment of inertia identified / M_inertia ident
SERVO Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: 25_1 Unit selection: p0100
Not for motor type: REL Expert list: 1
Min Max Factory setting
- [kgm²] - [kgm²] - [kgm²]